p2100[0...19]

Change fault response fault number / Chng resp F_no

TM150, TM15DI_DO,
Can be changed: U, T
TM31
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]

Change fault response response / Chng resp resp

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Integer16
CU_DC_S
P-Group: Messages
Not for motor type: -
Min
0
Description:
Sets the fault response for the selected fault.
Value:
0:
Dependency:
The fault is selected and the required response is set under the same index.
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]
Change fault response response / Chng resp resp
DC_CTRL,
Can be changed: U, T
DC_CTRL_R,
Data type: Integer16
DC_CTRL_R_S,
P-Group: Messages
DC_CTRL_S
Not for motor type: -
Min
0
Description:
Sets the fault response for the selected fault.
Value:
0:
1:
2:
3:
5:
6:
7:
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
NONE
NONE
OFF1
OFF2
OFF3
Reserved
Reserved
Reserved
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
0
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
7
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8075
Unit selection: -
Expert list: 1
Factory setting
0
163