Rfg Ramp-Down Time 3 / Rfg T_Ramp-Dn 3; Rfg Initial Rounding 3 / Rfg Init Rndg 3; Rfg Final Rounding 3 / Rfg Fin Rndg 3; Rfg Effective Times / Rfg T Effective - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p50312[0...n]

RFG ramp-down time 3 / RFG t_ramp-dn 3

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [s]
Description:
Sets the ramp-down time for ramp-function generator parameter set 3.
p50313[0...n]

RFG initial rounding 3 / RFG init rndg 3

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [s]
Description:
Sets the initial rounding for ramp-function generator parameter set 3.
Dependency:
Refer to: p50295
p50314[0...n]

RFG final rounding 3 / RFG fin rndg 3

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [s]
Description:
Sets the final rounding for ramp-function generator parameter set 3.
Dependency:
Refer to: p50295
r50315[0...3]

RFG effective times / RFG t effective

DC_CTRL
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
- [s]
Description:
Displays the effective times on the ramp-function generator.
Index:
[0] = Ramp-up time
[1] = Ramp-down time
[2] = Initial rounding
[3] = Final rounding
r50316
RFG state / RFG state
DC_CTRL
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the state on the ramp-function generator.
440
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
650.00 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 3150
Unit selection: -
Expert list: 1
Factory setting
10.00 [s]
Access level: 2
Func. diagram: 3150
Unit selection: -
Expert list: 1
Factory setting
0.00 [s]
Access level: 2
Func. diagram: 3150
Unit selection: -
Expert list: 1
Factory setting
0.00 [s]
Access level: 1
Func. diagram: 3150
Unit selection: -
Expert list: 1
Factory setting
- [s]
Access level: 1
Func. diagram: 3152
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading