p50083[0...n]

Speed controller actual value selection / n_ctr act sel

DC_CTRL
Can be changed: C2(1), T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Selection of the speed actual value.
Value:
0:
1:
2:
3:
4:
5:
Dependency:
Refer to: p50115, p50609
Warning:
If value = 3:
Monitoring for overspeed is only active subject to restrictions since if the EMF is used as the speed actual value with
a field current actual value which is too low, very high motor speeds will be reached.
Note:
If value = 3:
The EMF actual value is evaluated with p50115.
p50084
Closed-loop speed control/Closed-loop current/torque control sel / n/I/tqe ctr sel
DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
1
Description:
Sets closed-loop speed control or closed-loop current/torque control.
Value:
1:
2:
Note:
If value = 2:
The setpoint provided by the RFG output is set as the current/torque setpoint and the speed controller is bypassed.
p50085

Sequence control withdraw jog wait time / S ctr jog t

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [s]
Description:
Sets the wait time for sequence control once the jog command has been withdrawn.
Once the jog command has been withdrawn, the wait time does not start until n < n_min (p50370, p50371) is
reached.
Note:
Once a jog command has been withdrawn, the drive will remain in operating state o1.3 for the set wait time, with the
controllers inhibited and the line contactor picked up.
If a second jog command is sent during this time, the drive will switch to the next operating state (o1.2 or lower).
However, if the time elapses without a second jog command being sent, the line contactor will drop out and the drive
will switch to operating state o7.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Selection de-activated
Analog tachometer
Incr encoder
EMF actual value internal
Free interconnection using p50609
DRIVE-CLiQ encoder
Closed-loop speed control
Closed-loop current/torque control
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
5
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60.0 [s]
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 6810
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 6810, 6830
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 2651
Unit selection: -
Expert list: 1
Factory setting
10.0 [s]
393