Re bit 09:
When evaluating the encoder signals (track signals, zero marks, absolute values, ...) an illegal signal state was
detected. Check the encoder / state of the encoder signals. Observe the maximum frequencies.
Re bit 10:
The internal communication between the SINAMICS components is faulted or interrupted. Check the DRIVE-CLiQ
wiring. Ensure an EMC-compliant design. Observe the maximum permissible quantity structure / clock cycles.
Re bit 11:
The infeed is faulted or has failed. Check the infeed and the surroundings (line supply, filter, reactors, fuses, ...).
Check the closed-loop infeed control.
Re bit 15:
Group fault. Determine the precise cause of the fault using the commissioning tool.
r3114.9...11

CO/BO: Messages status word global / Msg ZSW global

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the global status word for messages.
The appropriate bit is set if at least one message is present at the drive objects.
Bit field:
Bit
09
10
11
Note:
The status bits are displayed with delay.
r3115[0...63]

Fault drive object initiating / F DO initiating

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Integer32
CU_DC_S, DC_CTRL,
P-Group: Messages
DC_CTRL_R,
Not for motor type: -
DC_CTRL_R_S,
DC_CTRL_S
Min
-
Description:
Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r3115[0...63]
Fault drive object initiating / F DO initiating
TM150, TM15DI_DO,
Can be changed: -
TM31
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Signal name
Group alarm present
Group fault present
Safety group message present
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
-
FP
8065
8060
-
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents