r0975[4] = 1401 --> 14th of January
r0975[5] = 1 --> PROFIdrive drive object, type class
r0975[6] = 9 --> PROFIdrive drive object sub-type class 1
r0975[7] = 2 --> drive object number = 2
r0975[8] = 0 (reserved)
r0975[9] = 0 (reserved)
r0975[10] = 600 --> second part, firmware version (complete version: V01.02.06.00)
p0976

Reset and load all parameters / Reset load all par

CU_DC, CU_DC_R,
Can be changed: C1(30)
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
Resets or downloads all parameters of the drive system.
Value:
0:
1:
2:
3:
10:
11:
12:
20:
100:
200:
1011: Start dnload of param. saved in volatile mem w/ p0977=1011
1012: Start dnload of param. saved in volatile mem w/ p0977=1012
1013: Start dnload of param. saved in volatile mem w/ p0977=1013
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
After executing p0976 = 200, the Control Unit is powered on automatically.
Note:
After all of the parameters have been reset to their factory setting, the system must be commissioned for the first time
again.
Resetting or loading is realized in the non-volatile memory.
Procedure:
1. Set p0009 = 30 (parameter reset).
2. Set p0976 to "required value". The system is rebooted.
p0976 is automatically set to 0 after execution.
p0977

Save all parameters / Save all par

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
Saves all parameters of the drive system to the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
Value:
0:
1:
10:
11:
12:
20:
80:
1011: Save in volatile memory, downloaded with p0976=1011
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Inactive
Start reset of all parameters to factory setting
Start dnload of param. saved in non-volatile mem w/ p0977=1
Start download of volatile parameters from RAM
Start dnload of param. saved in non-volatile mem w/ p0977=10
Start dnload of param. saved in non-volatile mem w/ p0977=11
Start dnload of param. saved in non-volatile mem w/ p0977=12
Start download Siemens internal setting 20
Start resetting of all BICO interconnections
Start deleting all user data
Inactive
Save in non-volatile memory - downloaded at POWER ON
Save as opt. in non-vol. memory - downloaded w/ p0976=10
Save as opt. in non-vol. memory - downloaded w/ p0976=11
Save as opt. in non-vol. memory - downloaded w/ p0976=12
Save in non-volatile memory as setting 20 (reserved)
Save in non-volatile memory time-optimized (reserved)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1013
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1013
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0