Bi: Signal Source For Device Fan Relay Output / Fan Relay Sig S; Delay Times For Device Fan Monitoring / Fan Mon T_Del; Field Device External Rated Direct Current / I_Rated Ext; External Field Monitoring / Ext Field Monit - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Note:
The parameter can only be changed for the Control Module.
If value = 1:
The input signal is available via binector output r53140.4 for further interconnection.
If value = 2:
The input signal is available via binector output r53140.3 for further interconnection.
p51834

BI: Signal source for device fan relay output / Fan relay sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the "Fan On" relay output (terminal 120/121) on the power interface.
Note:
The parameter can only be changed for the Control Module.
p51835[0...2]

Delay times for device fan monitoring / Fan mon t_del

DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [s]
Description:
Sets the delay times for device fan monitoring on the Control Module.
Index:
[0] = ON delay monitoring
[1] = ON delay fault
[2] = ON delay alarm
Dependency:
Refer to: A60266, F60267
Note:
The parameter can only be changed for the Control Module.
p51838

Field device external rated direct current / I_rated ext

DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [A]
Description:
Sets the rated direct current of an external field device (if there is one).
Dependency:
Refer to: p50082
Note:
This parameter is only effective if p50082 >= 21.
p51839

External field monitoring / Ext field monit

DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting for activating/de-activating the monitoring for the external field.
Value:
0:
1:
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Deactivated
Activated
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
600.00 [A]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6965, 8049
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8049
Unit selection: -
Expert list: 1
Factory setting
[0] 15.0 [s]
[1] 5.0 [s]
[2] 2.0 [s]
Access level: 2
Func. diagram: 6960, 6910
Unit selection: -
Expert list: 1
Factory setting
0.00 [A]
Access level: 2
Func. diagram: 8044
Unit selection: -
Expert list: 1
Factory setting
0
555