7.2.4

Select telegram

PROFIdrive telegrams
The following telegrams are available:
p0922 =
A more detailed depiction of the individual telegrams can be found in Section Cyclic
communication (Page 91).
Selecting a telegram
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.
7.2.5

Activating diagnostics via the control

The converter provides the functionality to transmit fault and alarm messages (diagnostic
messages) to the higher-level control according to the PROFIdrive error classes.
You must select the functionality in the higher-level control (see Manuals for your converter
(Page 292)) and activate it by booting up.
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
1:
Standard telegram 1, PZD-2/2 (factory setting)
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Extend telegrams and change signal interconnection (Page 98)
Configuring the fieldbus
7.2 Communication via PROFINET
87