Cud Analog Input 1 Offset / Cud Ai 1 Offs; Cud Analog Input 1 Signal Processing / Cud Ai 1 Sig Proc; Bi: Cud Analog Input 1 Inversion / Cud Ai 1 Inv; Cud Analog Input 1 Smoothing Time Constant / Cud Ai 1 T - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

The value indicates the percentage value for the mapping of an input voltage of 10 V or an input current of 20 mA at
the analog input.
Example:
p50711 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
p50712

CUD analog input 1 offset / CUD AI 1 offs

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the offset for analog input 1 (X177.27/28) on the CUD.
p50713

CUD analog input 1 signal processing / CUD AI 1 sig proc

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the signal processing mode for analog input 1 (X177.27/28) on the CUD.
Value:
0:
1:
2:
3:
p50714

BI: CUD analog input 1 inversion / CUD AI 1 inv

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for inverting the signal from analog input 1 (X177.27/28) on the CUD.
1 signal: Inversion
0 signal: No inversion
p50715

CUD analog input 1 smoothing time constant / CUD AI 1 T

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the time constant for smoothing the signal from analog input 1 (X177.27/28) on the CUD.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Signal not controlled
Signal absolute value generation
Signal inverted
Signal absolute value generation inverted
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000 [ms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2080
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 2
Func. diagram: 2080
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2080
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2080
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
503