r2146[0...63]

Alarm time removed in days / t_alarm res days

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the system runtime in days when the alarm was cleared.
Dependency:
Refer to: r2110, r2114, r2122, r2123, r2124, r2125, r2134, r2145, r3121, r3123
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
p2147

Delete fault buffer of all drive objects / Del fault buffer

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Integer16
CU_DC_S
P-Group: Displays, signals
Not for motor type: -
Min
0
Description:
Setting to delete the fault buffer of all existing drive objects.
Value:
0:
1:
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note:
p2147 is automatically set to 0 after execution.
r2197.3...7

CO/BO: Status word monitoring 1 / ZSW monitor 1

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned16
DC_CTRL_R_S,
P-Group: Messages
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Display and BICO output for the first status word of the monitoring functions.
Bit field:
Bit
03
07
r2199.1

CO/BO: Status word monitoring 3 / ZSW monitor 3

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned16
DC_CTRL_R_S,
P-Group: Messages
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Display and BICO output for the third status word of the monitoring functions.
Bit field:
Bit
01
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Inactive
Start to delete the fault buffer of all drive objects
Signal name
n_act >= 0
Speed setp - act val deviation in tolerance
t_off
Signal name
f or n comparison value reached or
exceeded
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2534
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
Access level: 2
Func. diagram: 2537
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
FP
8011
8011
FP
8010
181