aa = 08 hex = 8 dec:
A component was connected to a Control Unit that is not permitted for this purpose.
aa = 09 hex = 9 dec:
A component was connected to a Control Unit with out-of-date firmware.
aa = 0A hex = 10 dec:
Too many components of a particular type detected.
aa = 0B hex = 11 dec:
Too many components of a particular type detected on a single line.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Re fault cause = 1:
Change the configuration. Connect less than 199 components to the Control Unit.
Re fault cause = 2:
Remove the component with unknown component type.
Re fault cause = 3, 4, 5:
Establish a valid combination.
Re fault cause = 6, 7:
Connect the expansion module directly to a permitted Control Unit.
Re fault cause = 8:
Remove component or use a permissible component.
Re fault cause = 9:
Upgrade the firmware of the Control Unit to a later version.
Re fault cause = 10, 11:
Reduce the number of components.
A01361

Topology: Actual topology contains SINUMERIK and SIMOTION components

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The detected actual topology contains SINUMERIK and SIMOTION components.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: cc = fault cause, bb = component class of the actual topology, aa = component number of the
component
cc = 01 hex = 1 dec:
An NX10 or NX15 was connected to a SIMOTION control.
cc = 02 hex = 2 dec:
A CX32 was connected to a SINUMERIK control.
Remedy:
Re alarm value = 1:
Replace all NX10 or NX15 by a CX32.
Re alarm value = 2:
Replace all CX32 by an NX10 or NX15.
A01362

Topology: Topology rule(s) broken

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one topology rule for the SINAMICS S120 Combi has been broken.
In the event of a fault, the ramping up of the drive system is aborted and closed-loop drive control is not enabled.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms