Ci: Signal Source For Connector Recorder Function; Bi: Signal Source For Binector Recorder Function; Recorder Function Channel Selection / Rec Fct Sel; Recorder Function Recording Interval / Rec Fct T_Rec - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p51700[0...1]
CI: Signal source for connector recorder function / Rec fct con sig s
DC_CTRL
Can be changed: U, T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the connectors to be recorded by the recorder function.
Dependency:
Refer to: p51701, p51702, p51703, p51704, p51705, p51706
Note:
[0] = Signal source for the first connector to be recorded
[1] = Signal source for the second connector to be recorded
p51701[0...1]
BI: Signal source for binector recorder function / Rec fct bin sig s
DC_CTRL
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the binectors to be recorded by the recorder function.
Dependency:
Refer to: p51700, p51702, p51703, p51704, p51705, p51706
Note:
[0] = Signal source for the first binector to be recorded
[1] = Signal source for the second binector to be recorded
p51702

Recorder function channel selection / Rec fct sel

DC_CTRL
Can be changed: U, T
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Setting to select the channels to be recorded.
Bit field:
Bit
00
01
02
03
Dependency:
Refer to: p51700, p51701, p51703, p51704, p51705, p51706
p51703

Recorder function recording interval / Rec fct t_rec

DC_CTRL
Can be changed: U, T
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
1 [s]
Description:
Sets the recording interval,
during which the signals selected with the channel selection parameters (p51702.0 to 3) are scanned and saved
internally.
Dependency:
Refer to: p51700, p51701, p51702, p51704, p51705, p51706
540
Signal name
Channel 0
Channel 1
Channel 2
Channel 3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Active
Active
Active
Active
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000 [s]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 8050
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8050
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8050
Unit selection: -
Expert list: 1
Factory setting
1111 bin
0 signal
Not active
Not active
Not active
Not active
Access level: 2
Func. diagram: 8050
Unit selection: -
Expert list: 1
Factory setting
1 [s]
SINAMICS DCM
FP
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading