4 Faults and alarms
4.2 List of faults and alarms
F31153 (N, A)

Encoder 1: Identification error

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred when identifying the encoder (waiting) p0400=10100.
The connected encoder was not able to be identified.
Fault value (r0949, interpret hexadecimal):
Bit 0: Data length incorrect
See also: p0400 (Encoder type selection)
Remedy:
Manually configure the encoder according to the data sheet.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31160 (N, A)

Encoder 1: Analog sensor channel A failed

Message value:
%1
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
ENCODER (IASC/DCBRK, NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The input voltage of the analog sensor is outside the permissible limits.
Fault value (r0949, interpret decimal):
1: Input voltage outside detectable measuring range.
2: Input voltage outside the measuring range set in (p4673).
3: The absolute value of the input voltage has exceeded the range limit (p4676).
Remedy:
For fault value = 1:
- check the output voltage of the analog sensor.
For fault value = 2:
- check the voltage setting for each encoder period (p4673).
For fault value = 3:
- check the range limit setting and increase it if necessary (p4676).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F31161 (N, A)

Encoder 1: Analog sensor channel B failed

Message value:
%1
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
ENCODER (IASC/DCBRK, NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The input voltage of the analog sensor is outside the permissible limits.
Fault value (r0949, interpret decimal):
1: Input voltage outside detectable measuring range.
2: Input voltage outside the measuring range set in (p4675).
3: The absolute value of the input voltage has exceeded the range limit (p4676).
Remedy:
For fault value = 1:
- check the output voltage of the analog sensor.
For fault value = 2:
- check the voltage setting for each encoder period (p4675).