2 Parameters
2.2 List of parameters
If the deviation is less than this limit, then the pulse number is not corrected. If it is higher than this limit, fault F3x131
is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency:
Refer to: p0437, p4688
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
The positive limit describes additional pulses due to EMC.
p4682[0...n]
Zero mark monitoring tolerance window limit 1 negative / ZM tol lim 1 neg
DC_CTRL,
Can be changed: C2(4)
DC_CTRL_R,
Data type: Integer32
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
-1001
Description:
Sets the negative tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, the PPR is not corrected. If it is higher than this limit, fault F3x131 is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency:
Refer to: p0437, p4681, p4688
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -1001, the negated value of p4681 is effective.
The negative limit describes the pulses lost due to a covered glass panel in the incremental encoder.
p4683[0...n]
Zero mark monitoring tolerance window alarm threshold positive / ZM tol A_thr pos
DC_CTRL,
Can be changed: C2(4)
DC_CTRL_R,
Data type: Unsigned32
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
0
Description:
Sets the positive tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
If the zero mark deviation is higher than the tolerance set in p4681 and p4682 and fault F3x131 is re-parameterized
to alarm (A) or no message (N), the accumulator p4688 is compared with this parameter and, if applicable, alarm
A3x422 is output for 5 seconds.
Dependency:
Refer to: p0437, p4681, p4682, p4688
Note:
Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
p4684[0...n]
Zero mark monitoring tolerance window alarm threshold negative / ZM tol A_thr neg
DC_CTRL,
Can be changed: C2(4)
DC_CTRL_R,
Data type: Integer32
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
-100001
Description:
Sets the negative tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
If the zero mark deviation is higher than the tolerance set in p4681 and p4682 and fault F3x131 is re-parameterized
to alarm (A) or no message (N), the accumulator p4688 is compared with this parameter and, if applicable, alarm
A3x422 is output for 5 seconds.
Dependency:
Refer to: p0437, p4683, p4688
Note:
Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -100001, the negated value of p4683 is effective.
254
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
0
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
100000
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
0
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-1001
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-100001