p2112

BI: External alarm 1 / External alarm 1

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Unsigned32 / Binary
CU_DC_S, TM150,
P-Group: Messages
TM15DI_DO, TM31
Not for motor type: -
Min
-
Description:
Sets the signal source for external alarm 1.
Note:
An external alarm is triggered with a 1/0 signal.
p2112[0...n]
BI: External alarm 1 / External alarm 1
DC_CTRL,
Can be changed: U, T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Messages
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source for external alarm 1.
Note:
An external alarm is triggered with a 1/0 signal.
r2114[0...1]

System runtime total / Sys runtime tot

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned32
CU_DC_S
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the total system runtime for the drive unit.
The time comprises r2114[0] (milliseconds) and r2114[1] (days).
After r2114[0] has reached a value of 86.400.000 ms (24 hours) this value is reset and r2114[1] is incremented.
Index:
[0] = Milliseconds
[1] = Days
Dependency:
Refer to: r0948, r2109, r2123, r2125, r2130, r2136, r2145, r2146
Note:
The time in r2114 is used to display the times for faults and alarms.
When the electronic power supply is switched out, the counter values are saved.
After the drive unit is powered up, the counter continues to run with the last value that was saved.
p2116

BI: External alarm 2 / External alarm 2

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Unsigned32 / Binary
CU_DC_S, TM150,
P-Group: Messages
TM15DI_DO, TM31
Not for motor type: -
Min
-
Description:
Sets the signal source for external alarm 2.
Note:
An external alarm is triggered with a 1/0 signal.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1