Pb/Pn Diagnostics Clock Cycle Synchronism / Pb/Pn Diag Clock; If1 Pzd Maximum Interconnected / If1 Pzdmaxintercon; Pb/Pn Controller Sign Of Life Diagnostics / Pb/Pn Ctr Sol Diag; Response Receive Value After Pzd Failure / Resp Aft Pzd Fail - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

r2064[0...7]

PB/PN diagnostics clock cycle synchronism / PB/PN diag clock

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Integer32
CU_DC_S
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the last parameter received from the PROFIBUS/PROFINET controller for clock synchronism.
The parameters for clock synchronism are created when configuring the bus and are transferred at the start of cyclic
operation from the controller to the device.
Index:
[0] = Clock synchronous mode activated
[1] = Bus cycle time (Tdp) [µs]
[2] = Master cycle time (Tmapc) [µs]
[3] = Instant of actual value acquisition (Ti) [µs]
[4] = Instant of setpoint acquisition (To) [µs]
[5] = Data exchange interval (Tdx) [µs]
[6] = PLL window (Tpll-w) [1/12 µs]
[7] = PLL delay time (Tpll-d) [1/12 µs]
r2065

PB/PN controller sign of life diagnostics / PB/PN ctr SoL diag

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays how often the sign-of-life from the clock synchronous PROFIBUS/PROFINET controller last failed.
r2067[0...1]

IF1 PZD maximum interconnected / IF1 PZDmaxIntercon

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Display for the maximum interconnected PZD in the receive/send direction
Index 0: receive (r2050, r2060)
Index 1: send (p2051, p2061)
p2072

Response receive value after PZD failure / Resp aft PZD fail

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32
DC_CTRL_R_S,
P-Group: Communications
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the response for the receive value (r2090) after PZD failure.
Bit field:
Bit
00
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Signal name
Unconditionally open holding brake (p0855) Freeze value
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
Zero the value
FP
-
143

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents