2 Parameters
2.2 List of parameters
p0970

TM31 reset parameters / TM31 par reset

TM31
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 31 (TM31).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
1:
100:
Dependency:
Refer to: p0010
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
p0971

Save drive object parameters / Drv_obj par save

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S, DC_CTRL,
P-Group: Factory settings
DC_CTRL_R,
Not for motor type: -
DC_CTRL_R_S,
DC_CTRL_S
Min
0
Description:
Setting to save the parameter of the particular drive object in the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
Value:
0:
1:
Dependency:
Refer to: p0977, r3996
Caution:
If a memory card (optional) is inserted, the following applies:
The parameters are also saved on the card and therefore overwrite any existing data!
Notice:
The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
Note:
Starting from the particular drive object, the following parameters are saved:
CU3xx: Device-specific parameters and PROFIBUS device parameters.
Other objects: Parameters of the actual object and PROFIBUS device parameters.
Prerequisite:
In order that the parameter of a drive object, saved with p0971 = 1, is read the next time that the Control Unit is
booted, then all parameters must, as a minimum, have first been saved once with p0977 = 1.
p0971
Save drive object parameters / Drv_obj par save
TM150, TM15DI_DO,
Can be changed: U, T
TM31
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
Setting to save the parameter of the particular drive object in the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
112
Inactive
Start a parameter reset
Start a BICO interconnection reset
Inactive
Save drive object
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -