4 Faults and alarms
4.2 List of faults and alarms
A30044 (F)

Power unit: Overvolt 24/48 V alarm

Message value:
Channel: %1, voltage: %2 [0.1 V]
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the upper threshold has been violated.
Alarm value (r2124, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
Check the power supply of the power unit.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
F30045

Power unit: Supply undervoltage

Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Power supply fault in the power unit.
- The voltage monitor signals an undervoltage fault on the module.
The following applies for CU31x:
- the voltage monitoring on the DAC board signals an undervoltage fault on the module.
For S120M, the following applies:
- This message is displayed for undervoltage or overvoltage.
Remedy:
- Check the power supply of the power unit.
- carry out a POWER ON (power off/on) for the component.
- replace the module if necessary.
A30046 (F)

Power unit: Undervoltage alarm

Message value:
%1
Message class:
Power electronics faulted (5)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
Before the last restart, a problem occurred at the power unit power supply.
The voltage monitor in the internal FPGA of the PSA signals an undervoltage fault on the module.
Fault value (r0949, interpret decimal):
Register value of the voltage fault register.
Remedy:
- check the 24 V DC voltage supply to power unit.
- carry out a POWER ON (power off/on) for the component.
- replace the module if necessary.
Reaction upon F:
NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
F30050

Power unit: 24 V supply overvoltage

Message value:
-
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
The voltage monitor signals an overvoltage fault on the module.
980
List Manual (LH8), 02/2015, 6RX1800-0ED76