Emf Controller P Gain / Emf Ctr Kp; Emf Controller Integral Time / Emf Ctr Tn; Emf Controller Droop / Emf Ctr Droop; Emf Controller Pre-Control Setpoint Smoothing Time Constant - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Value:
0:
1:
Dependency:
Refer to: p50284
Note:
If value = 0:
The integral component of the EMF controller is kept constantly at zero (i.e. the EMF controller functions solely as a
proportional controller).
p50275[0...n]

EMF controller P gain / EMF ctr Kp

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.01
Description:
Sets the P gain of the EMF controller.
Dependency:
Refer to: p50276
Note:
The parameter is set automatically during the optimization run for field weakening (p50051 = 27).
p50276[0...n]

EMF controller integral time / EMF ctr Tn

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.010 [s]
Description:
Sets the integral time of the EMF controller.
Dependency:
Refer to: p50275
Note:
The parameter is set automatically during the optimization run for field weakening (p50051 = 27).
p50277[0...n]

EMF controller droop / EMF ctr droop

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [%]
Description:
Sets the value for the EMF controller's droop feedback.
Note:
If value = 0:
Droop feedback is de-activated.
p50280[0...n]
EMF controller pre-control setpoint smoothing time constant / EMF prec set T
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the smoothing time constant for the setpoint for EMF controller pre-control.
Dependency:
Refer to: p50283
Note:
This smoothing enables the EMF controller pre-control to be decoupled from the EMF controller.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Deactivated
Activated
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
10.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [ms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6900
Unit selection: -
Expert list: 1
Factory setting
0.60
Access level: 2
Func. diagram: 6900
Unit selection: -
Expert list: 1
Factory setting
0.200 [s]
Access level: 2
Func. diagram: 6900
Unit selection: -
Expert list: 1
Factory setting
0.0 [%]
Access level: 2
Func. diagram: 6900
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
433