Tm31 Inputs/Outputs Sampling Time / Tm31 I/O T_Sample; Tm150 Sensor Type / Tm150 Sensor Type - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The following applies for the sampling time:
The sampling times at a DRIVE-CLiQ line must be integral multiples of one another.
The sampling times of this TM must be an integral multiple of a servo or vector drive that exists in the system.
The minimum permissible sampling time is 125 µs.
Refer to: p0009, r0110, r0111
Note:
The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
Parameter p4099[0] must never be equal to zero.
p4099[0...2]

TM31 inputs/outputs sampling time / TM31 I/O t_sample

TM31
Can be changed: C1(3)
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the sampling time for the inputs and outputs of Terminal Module 31 (TM31).
Index:
[0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The following applies for the sampling time:
The sampling times at a DRIVE-CLiQ line must be integral multiples of one another.
The sampling times of this TM must be an integral multiple of a servo or vector drive that exists in the system.
The minimum permissible sampling time is 125 µs.
The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
Refer to: p0009, r0110, r0111
Notice:
The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
Note:
The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
Parameter p4099[0] must never be equal to zero.
p4100[0...11]

TM150 sensor type / TM150 sensor type

TM150
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the sensor type for Terminal Module 150 (TM150)
This means that the temperature sensor type is selected and the evaluation is switched in.
Value:
0:
1:
2:
4:
5:
6:
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
238
Evaluation disabled
PTC thermistor
KTY84
Bimetallic NC contact
PT100
PT1000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5000.00 [µs]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 9549, 9550
Unit selection: -
Expert list: 1
Factory setting
4000.00 [µs]
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
5
SINAMICS DCM