Remedy:
Assign the drive data set to different encoders.
See also: p0141 (Encoder interface (Sensor Module) component number), p0187 (Encoder 1 encoder data set
number), p0188 (Encoder 2 encoder data set number)
F07511

Drive: Encoder used a multiple number of times

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Each encoder may only be assigned to one drive and within a drive must - in each drive data set - either always be
encoder 1, always encoder 2 or always encoder 3. This unique assignment has been violated.
Fault value (r0949, interpret decimal):
The two parameters in coded form, that refer to the same component number.
First parameter:
Index: First and second decimal place (99 for EDS, not assigned DDS)
Parameter number: Third decimal place (1 for p0187, 2 for p0188, 3 for p0189, 4 for EDS not assigned DDS)
Drive number: Fourth and fifth decimal place
Second parameter:
Index: Sixth and seventh decimal place (99 for EDS, not assigned DDS)
Parameter number: Eighth decimal place (1 for p0187, 2 for p0188, 3 for p0189, 4 for EDS, not assigned DDS)
Drive number: Ninth and tenth decimal place
See also: p0141 (Encoder interface (Sensor Module) component number)
Remedy:
Correct the double use of a component number using the two parameters coded in the fault value.
F07512

Drive: Encoder data set changeover cannot be parameterized

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Using p0141, a changeover of the encoder data set is prepared that is illegal. In this firmware release, an encoder
data set changeover is only permitted for the components in the actual topology.
Alarm value (r2124, interpret decimal):
Incorrect EDS data set number.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number)
Remedy:
Every encoder data set must be assigned its own dedicated DRIVE-CLiQ socket. The component numbers of the
encoder interfaces (p0141) must have different values within a drive object.
The following must apply:
p0141[0] not equal to p0141[1] not equal to ... not equal to p0141[n]
F07515

Drive: Power unit and motor incorrectly connected

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A power unit (via PDS) was assigned to a motor (via MDS) in a drive data set that is not connected in the target
topology. It is possible that a motor has not been assigned to the power unit (p0131).
Fault value (r0949, interpret decimal):
Number of the incorrectly parameterized drive data set.
Remedy:
- assign the drive data set to a combination of motor and power unit permitted by the target topology.
- adapt the target topology.
- If required, for a missing motor, recreate the component (drive Wizard).
See also: p0121 (Power unit component number)
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
951