Remedy:
- power down/power up the power supply for the Control Unit.
- check the DRIVE-CLiQ connection.
- if required, replace the Terminal Module.
The Terminal Module should be directly connected to a DRIVE-CLiQ socket of the Control Unit.
If the fault occurs again, replace the Terminal Module.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A03501

TM: Sampling time change

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The sampling times of the inputs/outputs were changed.
This change only becomes valid after the next boot.
Remedy:
Carry out a POWER ON.
F03505 (N, A)

Analog input wire breakage

Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
CU_DC, CU_DC_R, CU_DC_R_S, CU_DC_S, TM150
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The wire-break monitoring for an analog input has responded.
The input current of the analog input has exceeded the threshold value parameterized in p4061[x].
Index x = 0: Analog input 0 (X521.1/X521.2)
Index x = 1: Analog input 1 (X521.3/X521.4)
Fault value (r0949, interpret decimal):
yxxx dec
y = analog input (0 = analog input 0 (AI 0), 1 = analog input 1 (AI 1))
xxx = component number (p0151)
Note:
For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 ... +20 mA)
Remedy:
- check the wiring for interruptions.
- Check the magnitude of the injected current - it is possible that the infed signal is too low.
- Check the load resistor (250 Ohm).
Note:
The input current measured by the Terminal Module can be read out from r4052[x].
For p4056[x] = 3 (unipolar current input monitored (+4 ... +20 mA)) the following applies:
A current less than 4 mA is not displayed in r4052[x] - but instead r4052[x] = 4 mA is output.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F03505 (N, A)
Analog input wire breakage
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The wire-break monitoring for an analog input has responded.
Remedy:
Check the wiring for interruptions.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
941