Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note:
When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
p0969
System runtime relative / t_System relative
CU_DC, CU_DC_R,
Can be changed: T
CU_DC_R_S,
Data type: Unsigned32
CU_DC_S
P-Group: Displays, signals
Not for motor type: -
Min
0 [ms]
Description:
Displays the system runtime in ms since the last POWER ON.
Note:
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970
TM150 reset parameters / TM150 par reset
TM150
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 150 (TM150).
Value:
0:
1:
100:
Dependency:
Refer to: p0010
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
p0970
TM15DI/DO reset parameter / TM15D par reset
TM15DI_DO
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 15 (TM15).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
1:
100:
Dependency:
Refer to: p0010
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Inactive
Start a parameter reset
Start a BICO interconnection reset
Inactive
Start a parameter reset
Start a BICO interconnection reset
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4294967295 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
111