p50254[0...n]
Field current controller integral component activation / I_field_ctr I comp
DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets activation/de-activation of the integral component on the field current controller.
Value:
0:
1:
Dependency:
Refer to: p50255, p50256
Note:
If value = 0:
The integral component of the field current controller is kept constantly at zero (i.e. the field current controller
functions solely as a proportional controller).
p50255[0...n]

Field current controller P gain / I_field ctr Kp

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.01
Description:
Sets the P gain of the field current controller.
Dependency:
Refer to: p50256
Note:
The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
p50256[0...n]

Field current controller integral time / I_field ctr Tn

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.001 [s]
Description:
Sets the integral time of the field current controller.
Dependency:
Refer to: p50255
Note:
The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
p50257[0...n]

Closed-loop field current control standstill field / If_ctr stst_field

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [%]
Description:
Sets the standstill field for closed-loop field current control.
Dependency:
Refer to: p50692
Note:
The field current is reduced to this value when the "Automatic field current reduction" function is parameterized
(p50082 = 2) or in the case of signal-driven selection of the ""Standstill excitation" function (p50692).
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Deactivated
Activated
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
100.0 [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6910
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 6908
Unit selection: -
Expert list: 1
Factory setting
5.00
Access level: 2
Func. diagram: 6908
Unit selection: -
Expert list: 1
Factory setting
0.200 [s]
Access level: 2
Func. diagram: 6910
Unit selection: -
Expert list: 1
Factory setting
0.0 [%]