p4062[0...1]
TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31
Can be changed: U, T
Data type: Unsigned16
P-Group: Terminals
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4063[0...1]

TM31 analog inputs offset / TM31 AI offset

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-20.000
Description:
Sets the offset for the analog inputs of Terminal Module 31 (TM31).
The offset is added to the input signal before the scaling characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4066[0...1]
TM31 analog inputs activate absolute value generation / TM31 AI absVal act
TM31
Can be changed: U, T
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31).
Value:
0:
1:
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4067[0...1]

BI: TM31 analog inputs invert signal source / TM31 AI inv s s

TM31
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Sets the signal source to invert the analog inputs signals of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
No absolute value generation
Absolute value generation switched in
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0.000
Access level: 3
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0