2 Parameters
2.2 List of parameters
p9903[0...n]

Target topology / Target topo

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0000 hex
Description:
Sets the target topology of the drive unit.
The target topology is sub-divided into several sections. Each of the following data is saved under an index.
General data on the topology:
- version
- attribute to compare the actual topology and target topology
- number of components
Data on a component:
- type component of the Node Identifier of the component
- number of DRIVE-CLiQ sockets in the Node Identifier
- manufacturer and version of the Node Identifier
- serial number of the Node Identifier (4 indices)
- index of the component
- order number (8 indices)
- attribute to compare the actual topology and target topology of the component
- component number
- number of port types
- port type
- number of ports of the port type
- component number of the associated/linked component
- number of the associated/linked port
- component number of the associated/linked component
- number of the associated port, etc.
Data on the next component:
- etc.
Dependency:
Refer to: p9902
Note:
The target topology can only be modified using the commissioning software.
The parameter is not displayed for the STARTER commissioning software.
Changes only become effective when the state of p0009 = 101 changes to 0 or 111.
p9904

Topology comparison acknowledge differences / Topo_compare ackn

CU_DC, CU_DC_R,
Can be changed: C1(1)
CU_DC_R_S,
Data type: Unsigned32
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0000 hex
Description:
If, when comparing the actual topology and target topology, only error has occurred, that can be acknowledged, then
using this parameter, a new comparison can be started - acknowledging the error in the target topology.
Differences that can be acknowledged:
- topology comparison, component shifted
- topology comparison, serial number of a component has been detected to be different (byte 3 = 1)
- topology comparison shows one component that is connected differently
360
Calculated: -
Dyn. index: p9902
Unit group: -
Scaling: -
Max
FFFF hex
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
FFFF FFFF hex
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex