Parameter listing
No.
Name/Value
01
01 Actual values
01.01
Motor speed used
-30000.00... 30000.00
rpm
01.03
Motor speed %
-1000.00... 1000.00%
01.06
Output frequency
-598.00...598.00 Hz
01.07
Motor current
0.00...30000.00
01.08
Motor current % of
motor nom
0.0...1000.0%
01.09
Motor current % of
drive nom
0.0...1000.0%
01.10
Motor torque
-1600.0...1600.0%
01.11
DC voltage
0.00...2000.00 V
01.13
Output voltage
0...2000 V
Description
Basic signals for monitoring the drive.
All parameters in this group are read-only unless
otherwise noted.
Note: Values of these actual signals are filtered with
the filter time defined in group
settings
. The selection lists for parameters in other
groups mean the raw value of the actual signal
instead. For example, if a selection is "Output
frequency" it does not point to the value of parameter
01.06 Output frequency
Estimated motor speed. A filter time constant for this
signal can be defined by parameter
motor speed
.
Estimated motor speed.
Actual speed in percent of the motor synchronous
speed. The filter time constant can be adjusted by
46.11 Filter time motor speed
parameter
Motor speed.
Estimated drive output frequency in Hz. A filter time
constant for this signal can be defined by parameter
46.12 Filter time output frequency
Estimated output frequency.
Measured (absolute) motor current in A.
Motor current.
Motor current (drive output current) in percent of the
nominal motor current.
Motor current.
Motor current (drive output current) in percent of the
nominal drive current.
Motor current.
Motor torque in percent of the nominal motor torque.
01.30 Nominal torque scale
See also parameter
A filter time constant for this signal can be defined by
46.13 Filter time motor torque
parameter
Motor torque.
Measured intermediate circuit DC Link voltage.
DC link voltage.
Calculated motor voltage in V AC.
Motor voltage.
46 Monitoring/scaling
but to the raw value.
46.11 Filter time
.
.
.
Parameters 93
Default
FbEq 16
-
See par.
46.01
-
See par.
46.01
-
See par.
46.02
-
See par.
46.05
-
1=1%
-
1=1%
-
.
See par.
46.03
-
10 = 1 V
-
1 = 1 V