Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
1
START
2
REVERSE
3
Reserved
4
RESET
5
EXT2
6
RUN_DISABLE
7
STOPMODE_RAM
P
8
STOPMODE_EME
RGENCY_RAMP
9
STOPMODE_COA
ST
10
Reserved for
RAMP_PAIR _2
11
RAMP_OUT_ZER
O
12
RAMP_HOLD
13
RAMP_IN_ZERO
14
REQ_LOCAL_LOC
K
15
Reserved for
TORQ_LIM_PAIR_
2
Value
1
0
1
Reverse direction of motor rotation.
0
0=>1
Fault reset if an active fault exists.
0
1
Select External control location EXT2. Effective if the
control location is parameterized to be selected from
0
Select External control location EXT1. Effective if the
control location is parameterized to be selected from
1
Run disable. If the drive is set to receive the run enable
signal from the fieldbus, this bit deactivates the
0
Run enable. If the drive is set to receive the run enable
signal from the fieldbus, this bit activates the signal.
1
0
(no op) Default to parameter stop mode if bits 7...9
1
0
(no op) Default to parameter stop mode if bits 7...9
1
0
(no op) Default to parameter stop mode if bits 7...9
1
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
0
1
Halt ramping (Ramp Function Generator output held).
0
1
Force Ramp Function Generator input to zero.
0
1
0
State/Description
Start the drive.
(no op)
(no op)
(no op)
the fieldbus.
the fieldbus.
signal.
Normal ramp stop mode
are all 0.
Emergency ramp stop mode.
are all 0.
Coast stop mode.
are all 0.
Not yet implemented.
Normal operation.
Normal operation.
Normal operation.
Not yet implemented.