ABB ACS280 Firmware Manual page 102

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

102 Parameters
No.
Name/Value
06
06 Control and status words
06.01
Main control word
0000h...FFFFh
Description
Drive control and status words.
The main control word of the drive. This parameter
shows the control signals as received from the
selected sources (such as digital inputs, the fieldbus
interfaces and the application program).
The bit assignments of the word are as described on
359
page
. The related status word are presented on
359
pages
.
This parameter is read-only.
Note: With the fieldbus control, the parameter value
is not same as the value that it receives from the PLC.
Bit
Name
0
Off1 control
1
Off2 control
2
Off3 control
3
Run
4
Ramp out zero
5
Ramp hold
6
Ramp in zero
7
Reset
8
Inching 1
9
Inching 2
10
Remote cmd
11
Ext ctrl loc
12
User bit 0
13
User bit 1
14
User bit 2
15
User bit 3
Main control word.
Default
FbEq 16
0000h
1 = 1