No.
Name/Value
37.22
ULC underload point 2
-1600.0...1600.0%
37.23
ULC underload point 3
-1600.0...1600.0%
37.24
ULC underload point 4
-1600.0...1600.0%
37.25
ULC underload point 5
-1600.0...1600.0%
37.31
ULC overload point 1
-1600.0...1600.0%
37.32
ULC overload point 2
-1600.0...1600.0%
37.33
ULC overload point 3
-1600.0...1600.0%
37.34
ULC overload point 4
-1600.0...1600.0%
37.35
ULC overload point 5
-1600.0...1600.0%
37.41
ULC overload timer
0.0...10000.0 s
37.42
ULC underload timer
0.0...10000.0 s
Description
Defines the second underload point.
37.21 ULC underload point 1
See parameter
Underload point.
Defines the third underload point.
37.21 ULC underload point 1
See parameter
Underload point.
Defines the fourth underload point.
37.21 ULC underload point 1
See parameter
Underload point.
Defines the fifth underload point.
37.21 ULC underload point 1
See parameter
Underload point.
Defines the first of the five points on the Y-axis that
together with the corresponding point on the X-axis
37.11 ULC speed table point 1
(
table point 5
37.15 ULC frequency table point
or
5
37.20 ULC frequency table point 5
...
overload (higher) curve.
At each of the five points the value of the underload
curve point must be equal to or smaller than the value
of the overload curve point. See parameter
underload point 1
.
Overload point.
Defines the second overload point.
37.31 ULC overload point 1
See parameter
Overload point.
Defines the third overload point.
37.31 ULC overload point 1
See parameter
Overload point.
Defines the fourth overload point.
37.31 ULC overload point 1
See parameter
Overload point.
Defines the fifth overload point.
37.31 ULC overload point 1
See parameter
Overload point.
Defines the time for which the monitored signal must
continuously stay above the overload curve before the
drive takes the action selected by
actions
.
Time.
Defines the time for which the monitored signal must
continuously stay below the underload curve before
the drive takes the action selected by
underload actions
.
Time.
Parameters 223
.
.
.
.
37.15 ULC frequency
...
) define the
37.21 ULC
.
.
.
.
37.03 ULC overload
37.04 ULC
Default
FbEq 16
15.0%
1 = 1%
25.0%
1 = 1%
30.0%
1 = 1%
30.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
300.0%
1 = 1%
20.0 s
1 = 1 s
20.0 s
1 = 1 s