136 Parameters
No.
Name/Value
20.30
Enable signals warning
function
Bit
Name
0
Enable to rotate
1
Run enable missing 1 = Warning
3...15
Reserved
0000h...FFFFh
21
21 Start/stop mode
21.01
Start mode
Fast
Const time
Description
Selects the enable signal warnings that will be
suppressed. This parameter can be used to prevent
these warnings from being added to the event log.
Whenever a bit of this parameter is set to 1, the
corresponding warning is suppressed.
Description
AFED Enable to rotate
1 = Warning
AFEB Run enable missing
Word for disabling enable signal warnings.
Start and stop modes; emergency stop mode and
signal source selection; DC magnetization settings.
Selects the motor start function for the vector motor
control mode, ie. when
Vector
set to
.
Notes:
• The start function for the scalar motor control
mode is selected by parameter
mode
.
• Starting into a rotating motor is not possible when
DC magnetizing is selected (
• With permanent magnet motors,
mode must be used.
• This parameter cannot be changed while the drive
is running.
DC magnetization
See also section
The drive pre-magnetizes the motor before start. The
pre-magnetizing time is determined automatically,
typically 200 ms to 2 s depending on motor size.
Select this mode if a high break-away torque is
required.
The drive pre-magnetizes the motor before start. The
pre-magnetizing time is defined by parameter
Magnetization time
. This mode should be selected if
constant pre-magnetizing time is required (e.g. if the
motor start must be synchronized with the release of
a mechanical brake). This setting also guarantees the
highest possible break-away torque when the pre-
magnetizing time is set long enough.
WARNING! The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In
applications where a full break-away torque is
essential, ensure that the constant magnetizing time
is long enough to allow generation of full
magnetization and torque.
is suppressed.
is suppressed.
99.04 Motor control mode
21.19 Scalar start
Fast
Const time
or
Automatic
51
on page
Default
FbEq 16
0000h
1 = 1
Const time
is
).
start
.
0
1
21.02