ABB ACS280 Firmware Manual page 190

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

190 Parameters
No.
Name/Value
Supervision 1
Supervision 2
Supervision 3
Supervision 4
Supervision 5
Supervision 6
EFB MCW bit 7
Other [bit]
31.12
Autoreset selection
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI supervision fault
4
Reserved
5
OverFrequency / Overspeed
6
Earth fault
7
Short circuit
8,9
Reserved
10
Selectable fault (see parameter
11
External fault 1 (from source selected by parameter
12
External fault 2 (from source selected by parameter
13
External fault 3 (from source selected by parameter
14
External fault 4 (from source selected by parameter
15
External fault 5 (from source selected by parameter
0000h...FFFFh
31.13
Selectable fault
0000h...FFFFh
Description
32.01 Supervision status.
Bit 0 of
32.01 Supervision status.
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Bit 3 of
32.01 Supervision status
Bit 4 of
32.01 Supervision status
Bit 5 of
Control word bit 7 received through the embedded
fieldbus interface.
Terms and abbreviations
Source selection (see
Selects faults that are automatically reset. The
parameter is a 16-bit word with each bit
corresponding to a fault type. Whenever a bit is set to
1, the corresponding fault is automatically reset.
The number and interval of reset attempts are
defined by parameters
WARNING! Before you activate the function,
make sure that no dangerous situations can
occur. The function resets the drive
automatically and continues operation after a fault.
Notes:
• The autoreset function is only available in external
control; see section
locations
26
(page
).
• Faults related to the Safe torque off (STO) function
cannot be automatically reset.
The bits of this binary number correspond to the
following faults:
31.13 Selectable fault
Automatic reset configuration word.
Defines the fault that can be automatically reset
31.12 Autoreset selection
using parameter
Faults are listed in chapter
Note: The fault codes are in hexadecimal. The
selected code must be converted to decimal for this
parameter.
Fault code.
.
.
.
.
31.14
31.16
...
.
Local and external control
)
31.01 External event 1 source
31.03 External event 2 source
31.05 External event 3 source
31.07 External event 4 source
31.09 External event 5 source
, bit 10.
Fault tracing
(page
Default
FbEq 16
24
25
26
27
28
29
32
).
-
0000h
)
)
)
)
)
1 = 1
0
327
).
10 = 1

Advertisement

Table of Contents
loading

Table of Contents