ABB ACS280 Firmware Manual page 211

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

No.
Name/Value
KTY84 analog I/O
1 x Pt100 analog I/O
2 x Pt100 analog I/O
3 x Pt100 analog I/O
Direct temperature
Description
KTY84 sensor connected to the analog input selected
35.14 Temperature 1 AI source
by parameter
analog output.
The following settings are required:
• Set the appropriate analog input unit selection
parameter in group
• In parameter group
selection parameter of the analog output to
sensor 1 excitation
.
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
Pt100 sensor connected to a standard analog input
selected by parameter
and an analog output.
The following settings are required:
• Set the hardware jumper or switch related to the
U
analog input to
(voltage). Any change must be
validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
• In parameter group
selection parameter of the analog output to
sensor 1 excitation
.
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
1 x Pt100 analog I/O
As selection
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
1 x Pt100 analog I/O
As selection
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
The temperature is taken from the source selected by
35.14
parameter
. The value of the source is assumed
to be in the unit of temperature specified by
parameter 96.16.
and an
12 Standard AI
V
to
(volt).
13 Standard AO
, set the source
35.14 Temperature 1 AI source
12 Standard AI
V
to
(volt).
13 Standard AO
, set the source
, but with two
, but with three
Parameters 211
Default
FbEq 16
2
Temp
5
Temp
6
7
11