ABB ACS280 Firmware Manual page 229

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

No.
Name/Value
40.21
Set 1 internal setpoint 1
-200000.00...
200000.00 PID
customer units
40.22
Set 1 internal setpoint 2
-200000.00...
200000.00 PID
customer units
40.23
Set 1 internal setpoint 3
-200000.00...
200000.00 PID
customer units
40.24
Set 1 internal setpoint 0
-200000.00...
200000.00 PID
customer units
40.26
Set 1 setpoint min
-200000.00...
200000.00
40.27
Set 1 setpoint max
-200000.00...
200000.00
40.28
Set 1 setpoint increase
time
0.0...1800.0 s
40.29
Set 1 setpoint decrease
time
0.0...1800.0 s
40.30
Set 1 setpoint freeze
enable
Not used
Used
DI1
DI2
Description
Internal process setpoint 1. See parameter
internal setpoint sel1
.
Internal process setpoint 1.
Internal process setpoint 2. See parameter
internal setpoint sel1
.
Internal process setpoint 2.
Internal process setpoint 3. See parameter
internal setpoint sel1
.
Internal process setpoint 3.
Internal process setpoint 0. See parameter
internal setpoint sel1
.
Internal process setpoint 0.
Defines a minimum limit for the process PID
controller setpoint.
Minimum limit for process PID controller setpoint.
Defines a maximum limit for the process PID
controller setpoint.
Maximum limit for process PID controller setpoint.
Defines the minimum time it takes for the setpoint to
increase from 0% to 100%.
Setpoint increase time.
Defines the minimum time it takes for the setpoint to
decrease from 100% to 0%.
Setpoint decrease time.
Freezes, or defines a source that can be used to
freeze, the setpoint of the process PID controller. This
feature is useful when the reference is based on a
process feedback connected to an analog input, and
the sensor must be serviced without stopping the
process.
1 = Process PID controller setpoint frozen
40.38 Set 1 output freeze enable
See also parameter
Process PID controller setpoint not frozen.
Process PID controller setpoint frozen.
10.02 DI delayed status
Digital input DI1 (
10.02 DI delayed status
Digital input DI2 (
Parameters 229
Default
FbEq 16
40.19 Set 1
0.00 PID
customer
units
1 = 1 PID
customer
unit
40.19 Set 1
0.00 PID
customer
units
1 = 1 PID
customer
unit
40.19 Set 1
0.00 PID
customer
units
1 = 1 PID
customer
unit
40.19 Set 1
0.00 PID
customer
units
1 = 1 PID
customer
unit
0.00
1 = 1
200000.00
1 = 1
0.0 s
1 = 1
0.0 s
1 = 1
not used
0
1
, bit 0).
2
, bit 1).
3