No.
Name/Value
46.02
Frequency scaling
0.10...1000.00 Hz
46.03
Torque scaling
0.1...1000.0%
46.04
Power scaling
0.10...30000.00
46.05
Current scaling
0...30000 A
46.06
Speed ref zero scaling
0.00 ... 30000.00 rpm
46.07
Frequency ref zero
scaling
0.00 ... 1000.00 Hz
46.11
Filter time motor speed
2...20000 ms
46.12
Filter time output
frequency
2...20000 ms
Description
Defines the maximum frequency value used to define
the acceleration ramp rate and the initial frequency
value used to define deceleration ramp rate (see
28 Frequency reference chain
parameter group
frequency acceleration and deceleration ramp times
are therefore related to this value (not to parameter
30.14 Maximum frequency
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds
to
20000 in eg. fieldbus communication.
Acceleration/deceleration terminal/initial frequency.
Defines the 16-bit scaling of torque parameters. The
value of this parameter (in percent of nominal motor
torque) corresponds to 10000 in eg. fieldbus
communication.
Torque corresponding to 10000 on fieldbus.
Defines the 16-bit scaling of power parameters. The
value of this parameter corresponds to 10000 in the
fieldbus communication. The unit is selected by
96.16 Unit selection
parameter
(For 32-bit scaling see
Power corresponding to 10000 on fieldbus.
Defines the 16-bit scaling of current parameters. The
value of this parameter corresponds to 10000 in
fieldbus, master/follower, etc. communication.
(For 32-bit scaling see
Current corresponding to 10000 on fieldbus.
Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface EFB). For example, with a
setting of 500, the fieldbus reference range of
0...20000 would correspond to a speed of
46.01
500...[
] rpm.
Note: This parameter is effective only with the ABB
Drives communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a frequency corresponding to a zero
reference received from fieldbus (either the
embedded fieldbus interface, or interface EFB). For
example, with a setting of 30, the fieldbus reference
range of 0...20000 would correspond to a speed of
46.02
30...[
] Hz.
Note: This parameter is effective only with the ABB
Drives communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a filter time for signals
used
.
Motor speed signal filter time.
Defines a filter time for signal
frequency
.
Output frequency signal filter time.
.
.
46.43 Power decimals
)
46.44 Current decimals
01.01 Motor speed
01.06 Output
Parameters 249
Default
FbEq 16
50.00 Hz
). The
10 = 1 Hz
100.0%
10 = 1%
1000.00
1 = 1 unit
10000 A
)
1 = 1 A
0.00 rpm
1 = 1 rpm
0.00 Hz
10 = 1 Hz
500 ms
1 = 1 ms
500 ms
1 = 1 ms