ABB ACS280 Firmware Manual page 199

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

No.
Name/Value
Fault if running
32.07
Supervision 1 signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Inverter temperature
Process PID output
Process PID feedback
Process PID setpoint
Process PID deviation
Other
32.08
Supervision 1 filter time
0.000 ... 30.000 s
32.09
Supervision 1 low
-21474830.00...
21474830.00
32.10
Supervision 1 high
-21474830.00...
21474830.00
32.11
Supervision 1
hysteresis
0.00...100000.00
32.15
Supervision 2 function
Disabled
Description
The drive trips on fault
running.
Selects the signal to be monitored by signal
supervision function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
.
01.10 Motor torque
.
01.11 DC voltage
.
01.14 Output power
.
12.11 AI1 actual value
.
12.21 AI2 actual value
.
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
05.11 Inverter temperature
40.01 Process PID output actual
40.02 Process PID feedback actual
40.03 Process PID setpoint actual
40.04 Process PID deviation actual
Terms and abbreviations
Source selection (see
Defines a filter time constant for the signal monitored
by signal supervision 1.
Signal filter time.
Defines the lower limit for signal supervision 1.
Low limit.
Defines the upper limit for signal supervision 1.
Upper limit.
Defines the hysteresis for the signal monitored by
signal supervision 1.
Note: This parameter applies to all selections of
32.05
parameter
, not just Hysteresis.
Hysteresis.
Selects the mode of signal supervision function 2.
Determines how the monitored signal (see parameter
32.17
) is compared to its lower and upper limits (
32.20
and
respectively). The action to be taken when
the condition is fulfilled is selected by
Signal supervision 2 not in use.
80B0 Signal supervision
.
.
.
.
.
.
.
.
.
.
.
.
32.16
.
Parameters 199
Default
FbEq 16
if
3
Frequency
0
1
3
4
6
7
8
9
10
18
19
20
21
22
23
24
25
26
27
).
-
0.000 s
1000 = 1 s
0.00
-
0.00
-
0.00
-
Disabled
32.19
0