ABB ACS280 Firmware Manual page 253

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

No.
Name/Value
47.23
Data storage 3 int16
-32768...32767
47.24
Data storage 4 int16
-32768...32767
49
49 Panel port communication
49.01
Node ID number
1...32
49.03
Baud rate
38.4 kbps
57.6 kbps
86.4 kbps
115.2 kbps
230.4 kbps
49.04
Communication loss
time
0.3...3000.0 s
49.05
Communication loss
action
No action
Fault
Last speed
Description
Data storage parameter 19.
16-bit data.
Data storage parameter 20.
16-bit data.
Communication settings for the control panel port on
the drive.
Defines the node ID of the drive. All devices connected
to the network must have a unique node ID.
Note: For networked drives, it is advisable to reserve
ID 1 for spare/replacement drives.
Note: Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
49.06 Refresh settings
by parameter
Node ID.
Defines the transfer rate of the link.
Note: Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
49.06 Refresh settings
by parameter
38.4 kbit/s.
57.6 kbit/s.
86.4 kbit/s.
115.2 kbit/s.
230.4 kbit/s.
Sets a timeout for control panel (or PC tool)
communication. If a communication break lasts
longer than the timeout, the action specified by
49.05 Communication loss action
parameter
Note: Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
49.06 Refresh settings
by parameter
Panel/PC tool communication timeout.
Selects how the drive reacts to a control panel (or PC
tool) communication break.
Note: Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
49.06 Refresh settings
by parameter
No action taken.
7081 Control panel loss
Drive trips on
A7EE Panel loss
Drive generates an
freezes the speed to the level the drive was operating
at. The speed is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Parameters 253
Default
FbEq 16
0
1 = 1
0
1 = 1
1
.
1 = 1
115.2 kbps
.
1
2
3
4
5
10.0 s
is taken.
.
10 = 1 s
Fault
.
0
.
1
warning and
2

Advertisement

Table of Contents
loading