348 Fault tracing
Code
Fault / Aux. code
(hex)
80B5
Signal supervision
(Editable message
text)
Programmable fault:
32.56 Supervision 6
action
9081
External fault 1
(Editable message
text)
Programmable fault:
31.01 External event 1
source
31.02 External event 1
type
9082
External fault 2
(Editable message
text)
Programmable fault:
31.03 External event
2 source
31.04 External event
2 type
9083
External fault 3
(Editable message
text)
Programmable fault:
31.05 External event
3 source
31.06 External event
3 type
9084
External fault 4
(Editable message
text)
Programmable fault:
31.07 External event
4 source
31.08 External event
4 type
9085
External fault 5
(Editable message
text)
Programmable fault:
31.09 External event
5 source
31.10 External event 5
type
FA81
Safe torque off 1
FA82
Safe torque off 2
Cause
Fault generated by the signal
supervision 6 function.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 5.
Fault in external device 5.
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Safe torque off function is
active, ie. STO circuit 2 is
broken.
What to do
Check the source of the fault
32.57 Supervision 6 signal
(parameter
Check the external device.
Check setting of parameter
External event 1 source
Check the external device.
Check setting of parameter
External event 2 source
Check the external device.
Check setting of parameter
External event 3 source
Check the external device.
Check setting of parameter
External event 4 source
Check the external device.
Check setting of parameter
External event 5 source
Check safety circuit connections. For
more information, see chapter
Safe torque off function
hardware manual of the drive and
description of parameter
indication run/stop
(page
).
31.01
.
31.03
.
31.05
.
31.07
.
31.09
.
The
in the
31.22 STO