196 Parameters
No.
Name/Value
31.33
Emergency ramp
supervision delay
0...100 s
31.40
Disable warning
messages
Bit
Name
0
Reserved
1
DC link undervoltage
2...4
Reserved
5
Emergency stop off2
4
Emergency stop off1, off3 1 = Warning
7...15
Reserved
0000h...FFFFh
31.54
Fault action
Coast
Emergency ramp
Description
31.32 Emergency ramp supervision
If parameter
to 0%, this parameter defines the maximum time an
emergency stop (mode Off1 or Off3) is allowed to
take. If the motor has not stopped when the time
elapses, the drive trips on
failed
06.17 Drive status word 2
, sets bit 8 of
coasts to a stop.
31.32
If
is set to a value other than 0%, this parameter
defines a delay between the receipt of the emergency
stop command and the activation of the supervision.
It is recommended to specify a short delay to allow
the speed change rate to stabilize.
Maximum ramp-down time, or supervision activation
delay.
Selects the warnings to be suppressed. This
parameter is a 16-bit word with each bit
corresponding to a warning. Whenever a bit is set to
1, the corresponding warning is not logged to event
log.
Description
1 = Warning
1 = Warning
suppressed.
Reserved
Word for disabling warnings.
Selects the stop mode when a non-critical fault
occurs.
The drive coasts to stop.
The drive follows the ramp specified for an
emergency stop by parameter
73B0 Emergency ramp
, and
A3A2 DC link undervoltage
AFE1 Emergency stop (off2)
AFE2 Emergency stop (off1 or off3)
23.23
.
Default
FbEq 16
is set
0 s
1 = 1 s
0000h
is suppressed.
is suppressed.
is
1 = 1
Coast
0
1