U/f
ratio
U
The
/f function is only available in scalar motor control mode, which uses
frequency control.
The function has two modes: linear and squared.
In linear mode, the ratio of voltage to frequency is constant below the field
weakening point. This is used in constant torque applications where it may be
necessary to produce torque at or near the rated torque of the motor
throughout the frequency range
In squared mode, the ratio of the voltage to frequency increases as the square
of the frequency below the field weakening point. This is typically used in
centrifugal pump or fan applications. For these applications, the torque
required follows the square relationship with frequency. Therefore, if the
voltage is varied using the square relationship, the motor operates at improved
efficiency and lower noise levels in these applications.
U
The
/f function cannot be used with energy optimization; if parameter
Energy optimizer
Settings and diagnostics

97.20 U/f ratio

Parameter
Events: -
37 User load curve
Enable
is set to
, parameter
284
(page
.
97.20 U/f ratio
).
Program features 49
45.11
is ignored.