Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
26...
Reserved
31
Status Word for the Transparent 32 Profile
Status word of the Transparent 32 profile can be read from the object 2004h.
Bit
Name
0
READY
1
ENABLED
2
Reserved for
ENABLED_TO_R
OTATE
3
RUNNING
4
ZERO_SPEED
5
ACCELERATING
6
DECELERATING
7
AT_SETPOINT
8
LIMIT
9
SUPERVISION
10
REVERSE_REF
11
REVERSE_ACT
12
PANEL_LOCAL
13
FIELDBUS_LOC
AL
Value
State/Description
Value
State/Description
1
Drive is ready to receive the start command.
0
Drive is not ready.
1
External run enable signal is active.
0
External run enable signal is not active.
Not yet implemented.
1
Drive is modulating.
0
Drive is not modulating.
1
Drive is at zero speed.
0
Drive is not at zero speed.
1
Not yet implemented.
0
Not yet implemented.
1
Not yet implemented.
0
Not yet implemented.
1
Drive is at setpoint.
0
Drive is not at setpoint.
1
Drive operation is limited.
0
Drive operation is not limited.
1
Actual value (speed, frequency or torque) is above a
limit. Limit is set with parameters 46.31...46.33
0
Actual value (speed, frequency or torque) is within
limits.
1
Not yet implemented.
0
Not yet implemented.
1
Not yet implemented.
0
Not yet implemented.
1
Panel/keypad (or PC tool) is in local control mode.
0
Panel/keypad (or PC tool) is not in local control mode.
1
Fieldbus is in local control mode.
0
Fieldbus is not in local control mode.