250 Parameters
No.
Name/Value
46.13
Filter time motor
torque
2...20000 ms
46.14
Filter time power
2...20000 ms
46.21
At speed hysteresis
0.00...30000.00 rpm
46.22
At frequency hysteresis
0.00...1000.00 Hz
Description
Defines a filter time for signal
Motor torque signal filter time.
Defines a filter time for signal
Output power signal filter time.
Defines the "at setpoint" limits for speed control of
the drive.
When the difference between reference (
reference act 7
) and the speed (
feedback
) is smaller than
the drive is considered to be "at setpoint". This is
06.11 Main status word
indicated by bit 8 of
Drive at setpoint
06.11
(
bit 8 = 1)
Limit for "at setpoint" indication in speed control.
Defines the "at setpoint" limits for frequency control
of the drive. When the absolute difference between
28.96 Frequency ref ramp input
reference (
01.06 Output frequency
frequency (
46.22 At frequency hysteresis
to be "at setpoint". This is indicated by bit 8 of
Main status word
.
Drive at setpoint
06.11
(
bit 8 = 1)
Limit for "at setpoint" indication in frequency control. See par.
01.10 Motor torque
01.14 Output power
22.87 Speed
24.02 Used speed
46.21 At speed hysteresis
.
24.02
(rpm)
22.87
46.21
+
(rpm)
22.87
(rpm)
22.87
46.21
-
(rpm)
0 rpm
) and actual
) is smaller than
, the drive is considered
06.11
01.06
(Hz)
28.96
46.22
+
(Hz)
28.96
(Hz)
28.96
46.22
-
(Hz)
0 Hz
Default
FbEq 16
.
100 ms
1 = 1 ms
.
100 ms
1 = 1 ms
50.00 rpm
,
See par.
46.01
2.00 Hz
46.02