Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
6
SWC_ON_
INHIB
7
ALARM
8
AT_
SETPOINT
9
REMOTE
10
ABOVE_
LIMIT
11
USER_0
12
USER_1
13
USER_2
14
USER_3
15
Status Word for the DCU Profile
The embedded fieldbus interface writes the drive Status Word bits 0 to 15 to
the fieldbus Status Word as is. Bits 16 to 32 of the drive Status Word are not in
use.
Bit
Name
0
READY
1
ENABLED
2
Reserved for
ENABLED_TO_R
OTATE
3
RUNNING
4
ZERO_SPEED
Value
1
0
1
0
1
OPERATING. Actual value equals Reference (is
within tolerance limits, e.g. in speed control, speed
error is 10% max. of nominal motor speed).
0
Actual value differs from Reference (is outside
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter). Valid in
both directions of rotation. Set by drive
parameters: 46.31, 46.32, 46.33. These parameters
are indicated by bit 10 of
0
Actual frequency or speed within supervision limit.
Status bits that can be combined with drive logic
for application-specific functionality.
Reserved
Value
1
Drive is ready to receive the start command.
0
1
External run enable signal is active.
0
External run enable signal is not active.
1
0
1
0
STATE/Description
SWITCH-ON INHIBITED.
–
Warning/Alarm.
No warning/alarm.
tolerance limits).
06.11 Main status
State/Description
Drive is not ready.
Not yet implemented.
Drive is modulating.
Drive is not modulating.
Drive is at zero speed.
Drive is not at zero speed.
363
word.