ABB ACS280 Firmware Manual page 260

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

260 Parameters
No.
Name/Value
Transparent 16
Transparent 32
58.26
EFB ref1 type
Speed or frequency
Transparent
General
Torque
Speed
Frequency
58.27
EFB ref2 type
58.28
EFB act1 type
Speed or frequency
Transparent
Description
Transparent control profile (with a 16-bit control
word).
Note: This selection is applicable only to CANopen.
Transparent control profile (with a 32-bit control
word).
Note: This selection is applicable only to CANopen.
Selects the type and scaling of reference 1 received
through the embedded fieldbus interface.
The scaled reference is displayed by
reference 1
.
Type and scaling is chosen automatically according to
the currently active operation mode as follows.
Operation mode
(see par.
Speed control
Torque control
Frequency control
No scaling is applied.
Generic reference without a specific unit.
Scaling: 1 = 100.
Torque reference. The scaling is defined by parameter
46.03 Torque scaling
Speed reference. The scaling is defined by parameter
46.01 Speed scaling
Frequency reference. The scaling is defined by
46.02 Frequency scaling
parameter
Selects the type and scaling of reference 2 received
through the embedded fieldbus interface.
The scaled reference is displayed by
reference 2
.
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus.network through the
embedded fieldbus interface.
Type and scaling is chosen automatically according to
the currently active operation mode as follows:
Operation mode
19.01
(see par.
)
Speed control
Torque control
Frequency control
The value selected by parameter
transparent source
scaling is applied (the 16-bit scaling is 1 = 1 unit).
03.09 EFB
Reference 1 type
19.01
)
Frequency
.
.
.
03.10 EFB
Actual 1 type (source)
Speed
01.01 Motor speed
(
used
)
Frequency
01.06 Output
(
frequency
)
58.31 EFB act1
is sent as actual value 1. No
Default
FbEq 16
8
9
Speed or
frequency
0
Speed
Speed
1
2
3
4
5
Speed or
frequency
Speed or
frequency
0
Scaling
46.01 Speed scaling
46.02 Frequency
scaling
1

Advertisement

Table of Contents