202 Parameters
No.
Name/Value
32.25
Supervision 3 function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
Description
Selects the mode of signal supervision function 3.
Determines how the monitored signal (see parameter
32.27
) is compared to its lower and upper limits (
32.30
and
respectively). The action to be taken when
the condition is fulfilled is selected by
Signal supervision 3 not in use.
Action is taken whenever the signal is below the
Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated whenever the signal is above
the Supervision 1 low limit + 0.5 * hysteresis.
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis.
Action is deactivated whenever the signal is below
the Supervision 1 high limit - 0.5 * hysteresis.
Action is taken whenever the absolute value of the
signal is below the absolute value of the Supervision 1
low limit - 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is above the absolute value of the
Supervision 1 low limit + 0.5 * hysteresis.
Action is taken whenever the absolute value of the
signal is above the absolute value of the Supervision 1
high limit + 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is below the absolute value of the
Supervision 1 high limit - 0.5 * hysteresis.
Action is taken whenever the signal is above the
Supervision 1 high limit + 0.5 * hysteresis or below
the Supervision 1 low limit - 0.5*hysteresis.
Action is deactivated whenever the signal is in
between the Supervision 1 high limit - 0.5 * hysteresis
and the Supervision 1 low limit + 0.5 * hysteresis.
Action is taken whenever the absolute value of the
signal is above the absolute value of the Supervision 1
high limit + 0.5 * hysteresis or below the absolute
value of the Supervision 1 low limit - 0.5 * hysteresis.
Action is deactivated whenever the absolute value
of the signal is in between the absolute value of the
Supervision 1 high limit - 0.5 * hysteresis and the
absolute value of the Supervision 1 low limit + 0.5 *
hysteresis.
Default
FbEq 16
Disabled
32.29
32.26
.
0
1
2
3
4
5
6