Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
12
PANEL_LOCAL
13
FIELDBUS_LOC
AL
14
EXT2_ACT
15
FAULT
References for the Transparent 16 profile
The reference values can be written to the objects 2052h and 2053h. The
references are scaled with the scaling value defined in
Actual values for the Transparent 16 profile
The actual values can be read from the objects 2055h and 2056h. The actual
values are scaled with the scaling value defined in
Transparent 32 profile
Control Word for the Transparent 32 Profile
Control word of the Transparent 32 profile can be written to the object 2001h.
The embedded fieldbus interface writes the fieldbus Control Word as is to the
drive.
Bit
Name
0
STOP
1
START
2
REVERSE
3
Reserved
4
RESET
5
EXT2
Value
State/Description
1
Panel/keypad (or PC tool) is in local control mode.
0
Panel/keypad (or PC tool) is not in local control mode.
1
Fieldbus is in local control mode.
0
Fieldbus is not in local control mode.
1
External control location EXT2 is active.
0
External control location EXT1 is active.
1
Drive is faulted.
0
Drive is not faulted.
0
No warning/alarm
Value
State/Description
1
Stop according to the Stop Mode parameter or the stop
mode request bits (bits 7...9).
0
(no op)
1
Start the drive.
0
(no op)
1
Reverse direction of motor rotation.
0
(no op)
0=>1
Fault reset if an active fault exists.
0
(no op)
1
Select External control location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External control location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
58.24 Transparent 16 scale
58.24 Transparent 16 scale
397
.
.