No.
Name/Value
96.06
Parameter restore
Done
Restore defaults
Clear all
Reset all fieldbus
settings
Reset home view
Reset end user texts
Reset motor data
All to factory defaults
Description
Restores the original settings of the control program,
ie. parameter default values.
Note: This parameter cannot be changed while the
drive is running.
Restoring is completed.
All editable parameter values are restored to default
values, except
• motor data and ID run results
• end user texts, such as customized warnings and
faults (external faults and changed), and the drive
name
• control panel/PC communication settings
• fieldbus adapter settings
95.20 HW options word 1
• parameter
differentiated defaults implemented by it.
• user lock configuration parameters
96.100
96.102
...
.
All editable parameter values are restored to default
values, except
• end user texts, such as customized warnings and
faults (external faults and changed), and the drive
name
• control panel/PC communication settings
• fieldbus adapter settings (clears entire existing
settings)
95.20 HW options word 1
• parameter
differentiated defaults implemented by it.
• user lock configuration parameters
96.100
96.102
...
.
PC tool communication is interrupted during the
restoring.
Restores all fieldbus and communication related
settings to default values.
Note: Fieldbus, control panel and PC tool
communication are interrupted during the restore.
Restores the Home view layout to show the values of
the default parameters.
Restores all end user texts to default values, including
the drive name, contact info, customized fault and
warning texts and currency unit.
If the value of parameter
then the PID unit is also reset. If parameter
some other value, the PID unit cannot be reset.
Restores all motor nominal values and motor ID run
results to default values.
Restores settings and all editable parameters back to
initial factory values, except
the differentiated defaults implemented by
parameter 95.20.
Parameters 273
and the
and the
40.79
User Text,
is set to
40.79
Default
FbEq 16
Done
0
8
62
32
512
1024
has
2
34560