ABB ACS280 Firmware Manual page 135

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

No.
Name/Value
Supervision 4
Supervision 5
Supervision 6
Other [bit]
20.26
Jogging 1 start source
Not used
Used
DI1
DI2
DI3
DI4
Supervision 1
Supervision 2
Supervision 3
Supervision 4
Supervision 5
Supervision 6
Other [bit]
20.27
Jogging 2 start source
20.28
Remote to local action
Keep running
Stop
Description
32.01 Supervision status
Bit 3 of
32.01 Supervision status
Bit 4 of
32.01 Supervision status
Bit 5 of
Terms and abbreviations
Source selection (see
If enabled by parameter
the source for the activation of jogging function 1.
(Jogging function 1 can also be activated through
fieldbus regardless of parameter
1 = Jogging 1 active.
Notes:
• Jogging is supported in vector control mode only.
• If both jogging 1 and 2 are activated, the one that
was activated first has priority.
• This parameter cannot be changed while the drive
is running.
0.
1.
10.02 DI delayed status
Digital input DI1 (
10.02 DI delayed status
Digital input DI2 (
10.02 DI delayed status
Digital input DI3 (
10.02 DI delayed status
Digital input DI4 (
32.01 Supervision status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Bit 3 of
32.01 Supervision status
Bit 4 of
32.01 Supervision status
Bit 5 of
Terms and abbreviations
Source selection (see
If enabled by parameter
the source for the activation of jogging function 2.
(Jogging function 2 can also be activated through
fieldbus regardless of parameter
1 = Jogging 2 active.
For the selections, see parameter
start source
.
Notes:
• Jogging is supported in vector control mode only.
• If both jogging 1 and 2 are activated, the one that
was activated first has priority.
• This parameter cannot be changed while the drive
is running.
Select the action to take when the drive switches
between remote and local control modes.
The drive will continue to run when the user changes
between the local and remote control of the drive. See
Local and external control locations
The drive will stop when the user changes between
the local and remote control of the drive. See
and external control locations
.
.
.
20.25 Jogging enable
, selects
20.25
.)
, bit 0).
, bit 1).
, bit 2).
, bit 3).
.
.
.
.
.
.
20.25 Jogging enable
, selects
20.25
.)
20.26 Jogging 1
26
(page
).
Local
26
(page
).
Parameters 135
Default
FbEq 16
27
28
29
).
-
not used
0
1
2
3
4
5
24
25
26
27
28
29
).
-
not used
Keep
running
0
1