Fieldbus control through the embedded fieldbus interface (EFB)
Reference
ABB Drives profile
33
Delayed status of digital
input DI2 (parameter
DI delayed
34
Delayed status of digital
input DI3 (parameter
DI delayed
35
Delayed status of digital
input DI4 (parameter
DI delayed
36
Delayed status of digital
input DO1 (parameter
DO delayed
Error code registers (holding registers 400090...400100)
These registers contain information about the last query. The error register is
cleared when a query has finished successfully.
Reference
89
Reset Error Registers
90
Error Function Code
91
92
Failed Register
93
Last Register Written
Successfully
94
Last Register Read
Successfully
10.02
status, bit 1)
10.02
status, bit 2)
10.02
status, bit 3)
11.02
status, bit 4)
Name
Error Code
• 00h No error
• 02h Low/High limit exceeded
• 03h Faulty Index: Unavailable index of an array
• 05h Incorrect Data Type: Value does not match the
• 65h General Error: Undefined error when handling
Delayed status of digital input DI2 (parameter
10.02 DI delayed
Delayed status of digital input DI3 (parameter
10.02 DI delayed
Delayed status of digital input DI4 (parameter
10.02 DI delayed
Delayed status of digital input DO1
(parameter
11.02 DO delayed
Description
1 = Reset internal error registers (91...95). 0 = Do
Function code of the failed query.
Set when exception code 04h is generated (see
table above).
parameter
data type of the parameter
query
The last register (discrete input, coil, input
register or holding register) that failed to be read
or written.
The last register (discrete input, coil, input
register or holding register) that was written
successfully.
The last register (discrete input, coil, input
register or holding register) that was read
successfully.
DCU Profile
status, bit 1)
status, bit 2)
status, bit 3)
status, bit 4)
nothing.
375