258 Parameters
No.
Name/Value
Fault always
Warning
58.15
Communication loss
mode
Any message
Cw / Ref1 / Ref2
58.16
Communication loss
time
0.0...6000.0 s
58.17
Transmit delay
0...65535 ms
58.18
EFB control word
0...FFFFFFFFh
Description
6681 EFB comm loss
Drive trips on
thought the drive is in a control location where the
EFB start/stop or reference is not used.
A7CE EFB comm loss
Drive generates an
occurs even though no control is expected from the
EFB.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Defines which message types reset the timeout
counter for detecting an EFB communication loss.
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
58.06 Communication control
by parameter
settings
).
58.14 Communication loss action
See also parameters
58.16 Communication loss time
and
58.01
Note: If parameter
parameter is hidden.
Any message addressed to the drive resets the
timeout.
A write of the control word or a reference resets the
timeout.
Sets a timeout for EFB communication. If a
communication break lasts longer than the timeout,
the action specified by parameter
Communication loss action
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
58.06 Communication control
by parameter
settings
).
58.15 Communication loss mode
See also parameter
Notes:
• There is a 30-second boot-up delay immediately
after power-up. During the delay, the
communication break monitoring is disabled (but
communication itself can be active).
58.01
• If parameter
= [3] CANopen, the default value
is set as 0.3 seconds.
EFB communication timeout.
Defines a minimum response delay in addition to any
fixed delay imposed by the protocol.
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
58.06 Communication control
by parameter
settings
).
58.01
Note: If parameter
parameter is hidden.
Minimum response delay.
Displays the raw (unmodified) status word sent by
the drive to the Modbus controller. For debugging
purposes.
This parameter is read-only.
Control word sent by the controller to the drive.
. This happens even
warning. This
Refresh
(
.
= [3] CANopen, this
58.14
is taken.
Refresh
(
Refresh
(
= [3] CANopen, this
Default
FbEq 16
4
5
Cw / Ref1 /
Ref2
1
2
3.0 s
.
1 = 1
0 ms
1 = 1
-
1 = 1