ABB ACS280 Firmware Manual page 391

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
2
RDY_REF
3
TRIPPED
4
OFF_2_STATUS
5
OFF_3_STATUS
6
SWC_ON_INHIB
7
ALARM
8
AT_SETPOINT
9
REMOTE
10
ABOVE_LIMIT
11
USER_0
12
USER_1
13
USER_2
14
USER_3
15
Reserved
References for the ABB Drives profile
The ABB Drives profile supports the use of two references, EFB reference 1 and
EFB reference 2. The references are 16-bit signed integers.
The reference values can be written to the objects 2102h and 2103h, or
alternatively to corresponding objects in the CiA 402 profile object area, see
(p.
Object dictionary
The references are scaled as defined by parameters
is in use depends on the setting of
the table
CANopen parameter settings for embedded fieldbus interface
Value
State/Description
1
OPERATION ENABLED.
0
OPERATION INHIBITED.
1
FAULT.
0
No fault.
1
OFF2 inactive.
0
OFF2 ACTIVE.
1
OFF3 inactive.
0
OFF3 ACTIVE.
1
SWITCH-ON INHIBITED.
0
1
Warning/Alarm.
0
No warning/alarm.
1
OPERATING. Actual value equals Reference (is within
tolerance limits, e.g. in speed control, speed error is
10% max. of nominal motor speed).
0
Actual value differs from Reference (is outside
tolerance limits).
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter). Valid in both
directions of rotation.
0
Actual frequency or speed within supervision limit.
Status bits that can be combined with drive logic for
application-specific functionality.
).
400
58.26 EFB ref1 type
...
; which scaling
46.01
46.04
and
58.27 EFB ref2 type
).
391